either a compressor or module is replaced. In this way
a record can be maintained and the user will be able
to assess the true history of the compressor. Using
the E2 Notebook feature is discussed in section 8.7.6
of the E2 Operation Manual.
5.8 Pressure Switch Replacement
The discharge and pressure switch adapters have
Schraeder valves in them. It is not necessary to
evacuate the compressor before replacing a switch. It
is imperative that an Emerson Climate Technologies,
Inc. approved pressure switch be used (see the part
number list in the Appendix). This will guarantee that
a Schraeder depressor is a part of the switch. The
Schraeder adapter enters the body with a 1/8” pipe
tap. Use a wrench to keep it from turning as the pres-
sure switch is loosened and removed from the
adapter, or while tightening the switch during installa-
tion.
Refer to figure 5.13 below.
Figure 5.13 Pressure Switch and Schraeder Adapter
5.9 “Hi-Pot” Testing
The motor may be electrically tested using a “Hi-Pot”
tester per Emerson Climate Technologies, Inc.
approved procedures without disconnecting the volt-
age sensing wires. If the high voltage Deutsch plug is
removed during test, be aware that several of the
exposed connector pins will have the tester voltage
on them.
5.10 Lifting Instructions
The recommended method to lift a compressor during
installation or removal is to install an eye-bolt in the
provided hole(s). If an eye-bolt is not available, a
strap may be used. However, care must be taken to
prevent damage to the sheet metal enclosures. Do
not attempt to lift the compressor with a strap around
the side box. Instead, the strap should be placed
behind the side box and directly around the compres-
sor as shown in figure 5.14. In order to position the
strap, it may be necessary to loosen or remove screw
“B” holding the side box to the terminal box.
Figure 5.14 Lifting Strap Placement
AE8-1337 R1