Reference Manual
00809-0600-4026, Rev BA
December 2011
2-9
Rosemount Process Radar
FOUNDATION fieldbus The Rosemount 5300 Series transmitter, FOUNDATION fieldbus version,
operates with power supply ranging from 9-32 Vdc (9-30 Vdc in IS
applications and 16-32 Vdc in Explosion-proof / Flameproof and in
Non-Sparking / Energy Limited applications). FISCO, IS applications: 9-17.5
Vdc.
Non-Intrinsically Safe Power Supply
NOTE
Rosemount 5300 Series Transmitters with Flameproof/Explosion-proof
Output have a built-in barrier; no external barrier needed.
Intrinsically Safe Power Supply
Power
Supply
Field Communicator
PC
Rosemount 5300 Series
Transmitter
Fieldbus
Modem
Power
Supply
Approved IS Barrier
Field Communicator
PC
Rosemount 5300
Series Transmitter
Fieldbus
Modem
For IS Parameters, see the Product Certifications chapter in the
Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530).