Reference Manual
00809-0600-4026, Rev BA
December 2011
3-11
Rosemount Process Radar
Recommended Actions:
• If bent probe, try to straighten it gently. If this is not possible, a
replacement of the complete probe assembly may be required
• Verify that mounting considerations described in the Rosemount 5300
Series Reference Manual (Document No. 00809-0100-4530) section
“Mounting Considerations” are fulfilled. The probe length should match
the tank/chamber length. For more information, refer to the Using
Guided Wave Radar for Level in High Pressure Steam Applications
Technical Note (Document No. 00840-0100-4530)
• Consider adding a centering disk at the bottom of the probe, for more
information see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “Mounting a Centering Disc
for Pipe Installations”. This helps to keep the probe centered in the
chamber/still-pipe. For more information, refer to the Using Guided
Wave Radar for Level in High Pressure Steam Applications Technical
Note (Document No. 00840-0100-4530)
• If flexible probe in contact with nozzle, consider using a long stud, for
more information see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “Mounting Considerations”.
Read Diagnostics
Verify that no Errors or unattended Warnings are present.
Figure 3-12. The Diagnostics
window in RRM
To view Diagnostics in Rosemount Radar Master:
Rosemount Radar Master > Tools > Diagnostics
For more information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “Diagnostics”.
Step 6. Archive Files Save Echo Curve and Config File
Permanently store the echo-curve and configuration back-up files for future
use, with re-occurring verification procedures.
In Rosemount Radar Master:
Rosemount Radar Master > Device > Backup Config to file
Rosemount Radar Master > Tools > Echo Curve > Record