Reference Manual
00809-0600-4026, Rev BA
December 2011
6-9
Rosemount Process Radar
2. Take a back-up of the plot including the reference/antenna echo
3. Review peak amplitudes
Verify that no disturbing echoes are present above the Surface
Threshold (ATC).
• Common Problems and Recommended Actions
Surface Threshold (ATC) is too low
If there are disturbing objects in the tank (e.g. nozzles, internal
obstructions, gaps between still-pipe modules) the threshold must be
set carefully to avoid locking on the wrong amplitude peak.
Figure 6-11. Surface threshold is
too low
Read Diagnostics
Verify that no Errors or unattended Warnings are present.
For more information, see the Rosemount 5400 Series Reference Manual
(Document No. 00809-0100-4026) section “Diagnostic Messages”.
• To view Diagnostics in Rosemount Radar Master:
Rosemount Radar Master > Tools > Diagnostics
Figure 6-12. The Diagnostics
window in Rosemount Radar
Master
Amplitude, mV
Actual surface
Surface Threshold=
Amplitude Threshold
Curve (ATC)
Distance, m
P1 - Disturbing echo
misinterpreted as
product surface
Reference