66 Transmitter Configuration and Use: Series 1000 and 2000 Transmitters
Required Transmitter Configuration continued
To configure the discrete output, see the menu flowcharts in Figure 6-13. Note that if you want to
configure polarity for the discrete output, you must use ProLink II.
Figure 6-13 Configuring the discrete output(s)
Table 6-15 Discrete output assignments and output levels
Assignment
ProLink II
code
Communicator
code
Display
code Condition
Discrete
output level
(1)
(1) Voltage descriptions in this column assume that Polarity is set to Active high. If Polarity is set to Active low, the voltages are reversed.
Event 1 (see Section 8.10) Event 1 Event 1 EVNT1 ON Site-specific
OFF 0V
Event 2 (see Section 8.10) Event 2 Event 2 EVNT2 ON Site-specific
OFF 0V
Event 1 or Event 2 Event 1 or
Event 2
Event1 or Event2 E1OR2 ON Site-specific
OFF 0V
Flow switch
(2)
(2) See Section 6.7.1.
Flow Switch Flow Switch FLSWT ON Site-specific
OFF 0V
Flow direction Fwd/Rev Forward/Reverse FLDIR Forward 0V
Reverse Site-specific
Calibration in progress Cal in Progress Calibration in progr ZERO ON Site-specific
OFF 0V
Fault Fault Fault FAULT ON Site-specific
OFF 0V
Communicator DisplayProLink II
Frequency/Discrete output
Configuration
On-Line Menu
Detailed Setup
Config outputs
FO/DO config
Off-line maint
Off-line configure
Configure DO1/DO2
Discrete IO
AN and IS transmitters CIO transmitters
DI/DO setup
AN and IS transmitters CIO transmitters
ProLink Menu