88 Transmitter Configuration and Use: Series 1000 and 2000 Transmitters
Optional Configuration continued
Note: Most users should select the Normal update rate. Use the Special update rate only if required
by your application. Contact Micro Motion before setting the update rate to Special.
Note: If you change the update rate, the setting for damping is automatically adjusted. See
Section 8.7.3.
8.9 Configuring the flow direction parameter
The flow direction parameter controls how the transmitter reports flow rate and how
flow is added to or subtracted from the totalizers, under conditions of forward flow,
reverse flow, or zero flow.
Forward (positive) flow moves in the direction of the arrow on the sensor.
Reverse (negative) flow moves in the direction opposite of the arrow on the
sensor.
Options for flow direction include:
Forward only
•Reverse only
Absolute value
Bidirectional
Negate/Forward only (Model 1500/2500 transmitters only)
Negate/Absolute value (Model 1500/2500 transmitters only)
For the effect of flow direction on mA outputs:
See Figure 8-1 if the 4 mA value of the mA output is set to 0.
See Figure 8-2 if the 4 mA value of the mA output is set to a negative value.
For a discussion of these figures, see the examples following the figures.
For the effect of flow direction on frequency outputs, totalizers, and flow values reported via digital
communication, see Table 8-6.
Model 1500 AN
Model 1700 AN
Model 1700 IS
Model 2500 CIO
Model 2700 AN
Model 2700 IS
Model 2700 CIO