Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 11 of 149
RTU Framing
The example below shows a typical Q/R from a SiteLink module. In common terms, the master device initiates a
query asking slave device 2 for holding registers starting at holding register 40051 (decimal 50) and including
next 2 Registers (3 total).
Query Sample
Slave
Address
Function
Code
Starting
Register
―Hi Byte‖
Starting
Register
―Lo Byte‖
Number of
Registers
―Hi Byte‖
Number of
Registers
―Lo Byte‖
CRC16
―Hi Byte‖
CRC16
―Lo Byte‖
02
03
00
32
00
03
E5
FA
Response Sample
Slave
Address
Function
Code
Count:
Bytes of
Data
Register
40051 Data
Hi Lo
Register
40052 Data
Hi Lo
Register
40053 Data
Hi Lo
CRC16
―Hi Byte
CRC16
―Lo Byte‖
02
03
6
01 58
00 FA
00 54
1B
0D
Slave address 2 responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.
Register values: 40051 = 158(hex) = 344(decimal)
40052 = FA (hex) = 250 (decimal)
40053 = 54 (hex) = 84 (decimal)
ASCII Framing:
Framing in ASCII transmission mode is accomplished by the use of the unique colon (:) to indicate the beginning of the
frame and a carriage return (CR) line feed (LF) to delineate the end of the frame. The line feed also serves as a
synchronizing character which indicates that the transmitting station is ready to receive an immediate reply.
ASCII Example
Frame
Start
Slave
Address
Function
Code
Data
Error
Check
End of
Frame
CR
Ready for
Data
LF
:
2 Char
16-bits
2 Char
16-bits
N x 4 Char
N x 16-bits
B3
0D
0A
Char = Character: 1 Character = 7 data bits, 1 start bit, 1 or 2 stop bits and 1 parity bit (optional)