Emerson Autochangeover Controllers AC8 Manual do Utilizador Página 112

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 149
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 111
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 112 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Inverter Status
Utility Status
Bypass Status
Battery Test in Progress
Battery Time Remaining
40020
20
BS20_x
Countdown starts at 254
KVA Size
40019
19
BS19_x
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Bypass Failure
40289:01
289:01
BA01_x:01
Input Failure
40289:02
289:02
BA01_x:02
Battery Discharging
40289:03
289:03
BA01_x:03
Low Battery Reserve
40289:04
289:04
BA01_x:04
Output Overload
40289:05
289:05
BA01_x:05
Ambient Overtemperature
40289:06
289:06
BA01_x:06
Output Undervoltage
40289:07
289:07
BA01_x:07
Output Overvoltage
40289:08
289:08
BA01_x:08
Input Overvoltage
40289:09
289:09
BA01_x:09
Charge Failure
40289:10
289:10
BA01_x:10
UPS Off
40290:00
290:00
BA02_x:00
Load On Bypass
40290:01
290:01
BA02_x:01
Utility Failed
40290:02
290:02
BA02_x:02
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Bypass Voltage A-N
Bypass Voltage B-N
Bypass Voltage C-N
Voltage In A-N
Voltage In B-N
Vista de página 111
1 2 ... 107 108 109 110 111 112 113 114 115 116 117 ... 148 149

Comentários a estes Manuais

Sem comentários