Emerson Autochangeover Controllers AC8 Manual do Utilizador Página 68

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 149
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 67
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 68 of 149
Power Unit Power Monitoring Panel (Ext. Protocol PM2)
Hardware Compatibility
Liebert Units:
Datawave, Precision Power Center
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Voltage In X-Y
40001
1
BS01_x
Voltage In Y-Z
40002
2
BS02_x
Voltage In Z-X
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage Out A-N
40007
7
BS07_x
Voltage Out B-N
40008
8
BS08_x
Voltage Out C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
Ground Current
40013
13
BS13_x
Divide by 10 for correct value
Neutral Current
40014
14
BS14_x
KVA
40015
15
BS15_x
KW
40016
16
BS16_x
Frequency
40017
17
BS17_X
Divide by 10 for correct value
% Capacity A
40018
18
BS18_x
% Capacity B
40019
19
BS19_x
% Capacity C
40020
20
BS20_x
Power Factor
40021
21
BS21_x
Divide by 100 for correct value
Kilowatt Hours
THD Voltage X
THD Voltage Y
THD Voltage Z
THD Current X
THD Current Y
Vista de página 67