Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 55 of 149
Point Availability
SiteScan
Modbus
Register
BACnet
Object
Notes:
Alarm Points (cont.)
Alarm I (Word cont.)
40289
BA1
Compressor 1 Overload
bit7
BA07
Compressor 1 Pumpdown Fail
bit8
BA08
Compressor 2 High Pressure
bit5
BA09
Ored with bit5 (Comp 1 HP)
Compressor 2 Low Pressure
bit6
BA0A
Ored with bit6 (Comp 1 LP)
Compressor 2 Overload
bit7
BA0B
Ored with bit7 (Comp 1 OL)
Compressor 2 Pumpdown Fail
bit8
BA0C
Ored with bit8 (Comp 1 PF)
DigiScroll 1 High Temp
bit9
BA0D
DigiScroll 2 High Temp
bit9
BA0E
Ored with bit9 (DigiScroll 1 HT)
Smoke Detected
bit10
BA0F
Water Detected
bit11
ba10
Humidifier Problem
bit12
ba11
Standby Glycol Pump On
bit13
ba12
Standby Glycol Unit On
bit14
ba13
Condenser Pump High Water
bit15
ba14
Alarm II (Word)
40290
BA2
Room Sensor Fail
bit0
ba15
Compressor Loss Of Power
bit1
ba16
Blower Fail
bit2
ba17
Emergency Damper Fail
bit3
ba18
Internal High Temperature
bit4
ba19
Humidifier Water Low
bit5
ba1a
Humidifier High Current
bit6
ba1b
User High Temperature
bit7
ba1c
Loss Of Power
bit8
ba1d
High Chilled Water Temp
bit9
ba20
High Electric Heater Temp
bit10
ba21
High Room Temp
bit11
ba22
Low Room Temp
bit12
ba23
High Room Humidity
bit13
ba24
Low Room Humidity
bit14
ba25
Sensor A High Temp
bit15
ba26
Alarm III (Word)
40291
BA3
Sensor A Low Temp
bit0
ba27
Sensor A High Humidity
bit1
ba28
Sensor A Low Humidity
bit2
ba29
Loss Of Chilled Water Flow
bit3
ba2a
Clogged Air Filters
bit4
ba2b
Internal Low Temp
bit5
ba2c
High External Dewpoint
bit6
ba2d
Supply Sensor Fail
bit7
ba30