Emerson Autochangeover Controllers AC8 Manual do Utilizador Página 140

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 149
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 139
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 140 of 149
Remote Autochangeover RAC
Hardware Compatibility
Liebert Units:
RAC2-8
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Unit 1
40001
1
BS01_x
1=on / 0=0ff
Unit 2
40002
2
BS02_x
1=on / 0=0ff
Unit 3
40003
3
BS03_x
1=on / 0=0ff
Unit 4
40004
4
BS04_x
1=on / 0=0ff
Unit 5
40005
5
BS05_x
1=on / 0=0ff
Unit 6
40006
6
BS06_x
1=on / 0=0ff
Unit 7
40007
7
BS07_x
1=on / 0=0ff
Unit 8
40008
8
BS08_x
1=on / 0=0ff
Alarm Points
Communications
40289:0
289:0
BA01_x:00
Common Alarm 1
40289:1
289:1
BA01_x:01
Common Alarm 2
40289:2
289:2
BA01_x:02
Common Alarm 3
40289:3
289:3
BA01_x:03
Common Alarm 4
40289:4
289:4
BA01_x:04
Common Alarm 5
40289:5
289:5
BA01_x:05
Common Alarm 6
40289:6
289:6
BA01_x:06
Common Alarm 7
40289:7
289:7
BA01_x:07
Common Alarm 8
40289:8
289:8
BA01_x:08
Emergency Power Operation
40289:9
289:9
BA01_x:09
EPO All Units
40289:10
289:10
BA01_x:10
High Temperature
40290:0
290:0
BA02_x:00
Low Temperature
40290:1
290:1
BA02_x:01
High Humidity
40290:2
290:2
BA02_x:02
Low Humidity
40290:3
290:3
BA02_x:03
Manual Override
40290:4
290:4
BA02_x:04