Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 14 of 149
BACnet Standard Application Services Supported (continued):
Object Type
Supported
Dynamically
Creatable
Dynamically
Deleteable
Optional
Properties
Writable
Properties
Analog Input
X
None
Analog Output
X
Present Value
Analog Value
Binary Input
Binary Output
Binary Value
Calendar
Command
Device
Event Enrollment
File
Group
Loop
Multi-State Input
Multi-State Output
Notification Class
Program
Schedule
Data Link Layer:
Point-to-Point, EIA-232, baud rates: 9600 & 38,400
Character Set Supported:
ANSI X3.4
Special Functionality:
Segmented Requests Supported
No
Segmented Responses Supported
No
Router
No