Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 126 of 149
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (Set)
None
Alarm Points
Loss Of Communications
40289:00
BA01_x:00
Load On Battery
40289:01
BA01_x:01
Load On Bypass
40289:02
BA01_x:02
Overload Bypass
40289:03
BA01_x:03
Fault Bypass
40289:04
BA01_x:04
Manual Bypass
40289:05
BA01_x:05
Manual Xfer Prohibited
40289:06
BA01_x:06
UPS Overload
40289:07
BA01_x:07
Shutdown Pending
40289:08
BA01_x:08
Battery Shutdown imminent
40289:09
BA01_x:09
Fan Fail
40289:10
BA01_x:10
Air Filter Bad
40289:11
BA01_x:11
Transformer Overtemperature
40289:12
BA01_x:12
Internal Comm Failure
40289:13
BA01_x:13
New Event Logged
40289:14
BA01_x:14
Input Power Failure
40289:15
BA01_x:15
Red Power Module Low
40290:00
BA02_x:00
Device Active Alarm
40290:01
BA02_x:01
Main Control Module Alarm
40290:02
BA02_x:02
Redundant Module Alarm
40290:03
BA02_x:03
Power Module Alarm
40290:04
BA02_x:04
Battery Module Alarm
40290:05
BA02_x:05
Main Control Module Fail
40290:06
BA02_x:06
Red. Control Module Fail
40290:07
BA02_x:07
User Interface Module Fail
40290:08
BA02_x:08
Power Module Failure
40290:09
BA02_x:09
Battery Module Failure
40290:10
BA02_x:10
Overtemp Shutdown
40290:11
BA02_x:11
Overload Shutdown
40290:12
BA02_x:12
Output Short Shutdown
40290:13
BA02_x:13
Low Battery Shutdown
40290:14
BA02_x:14
Remote Shutdown
40290:15
BA02_x:15
EPO Shutdown
40291:00
BA03_x:00