Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 92 of 149
UPS Unit Single Module Series SMS
Hardware Compatibility
Liebert Units:
Series 300/500/600 Single Module UPS
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Voltage In A-B
40001
1
BS01_x
Voltage In B-C
40002
2
BS02_x
Voltage In C-A
40003
3
BS03_x
Voltage Out A-B
40004
4
BS04_x
Voltage Out B-C
40005
5
BS05_x
Voltage Out C-A
40006
6
BS06_x
Voltage Out A-N
40007
7
BS07_x
Voltage Out B-N
40008
8
BS08_x
Voltage Out C-N
40009
9
BS09_x
Current Out A
40010
10
BS10_x
Current Out B
40011
11
BS11_x
Current Out C
40012
12
BS12_x
DC Bus Voltage
40013
13
BS13_x
DC Bus Current
40014
14
BS14_x
KVA
40015
15
BS15_x
Divide by 10 for correct value
Modbus Only
KW
40016
16
BS16_x
Divide by 10 for correct value
Modbus Only
Frequency
40017
17
BS17_x
Divide by 10 for correct value
Modbus Only
% Capacity Phase A
40018
18
BS18_x
% Capacity Phase B
40019
19
BS19_x
% Capacity Phase C
40020
20
BS20_x
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Battery Discharge
40289:01
289:01
BA01_x:01
Low Battery Reserve
40289:02
289:02
BA01_x:02
Output Overload
40289:03
289:03
BA01_x:03
Fuse Cleared
40289:04
289:04
BA01_x:04
Emergency Power Off
40289:05
289:05
BA01_x:05
Ambient Overtemperature
40289:06
289:06
BA01_x:06
Load On Bypass
40289:07
289:07
BA01_x:07
Static Switch Disabled
40289:08
289:08
BA01_x:08
Battery Disconnected
40289:09
289:09
BA01_x:09
Module Cooling Failure
40289:10
289:10
BA01_x:10