Emerson Autochangeover Controllers AC8 Manual do Utilizador Página 87

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 149
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 86
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 87 of 149
UPS Unit System Control Cabinet S/610 Ext. Prot. SC4
Hardware Compatibility
Liebert Units:
Series /610 SCC
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Input Voltage A-B
40001
1
BS01_x
Input Voltage B-C
40002
2
BS02_x
Input Voltage C-A
40003
3
BS03_x
Output Voltage A-B
40004
4
BS04_x
Output Voltage B-C
40005
5
BS05_x
Output Voltage C-A
40006
6
BS06_x
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
40007
7
BS07_x
Output Amps Phase B
40008
8
BS08_x
Output Amps Phase C
40009
9
BS09_x
KVA
40010
10
BS10_x
KW
40011
11
BS11_x
Critical Bus Frequency
40012
12
BS12_x
Divide by 10 for correct value
% Capacity Phase A
40013
13
BS13_x
% Capacity Phase B
40014
14
BS14_x
% Capacity Phase C
40015
15
BS15_x
Bypass Voltage A-B
40016
16
BS16_x
Bypass Voltage B-C
40017
17
BS17_x
Bypass Voltage C-A
40018
18
BS18_x
Output Frequency
40019
19
BS19_x
Divide by 10 for correct value
Bypass Frequency
40020
20
BS20_x
Divide by 10 for correct value
Total Operating Hours
Number of Modules in
System
System Number
Vista de página 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 148 149