Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 53 of 149
Air Unit iCOM DS & Retrofit (16mb version SiteLink)
Hardware Compatibility
Liebert Units:
iCOM DS controls and retrofit using IS485 communication interface card
SiteScan Interface Modules:
SiteLink-E
BMS interface Modules:
SiteLink-E
Point Availability
SiteScan
Modbus
Register
BACnet
Object
Notes:
Status Points
Unit On/Off
40001
BS1
Unit Standby
40002
BS2
Cooling State
40003
BS03b1
Fan State
-
BS03b0
Free Cooling State
-
BS03b2
Hot Water State
-
BS03b3
Electrical Heater State
40004
BS03b4
Fan Ramp %
-
BS04
Cooling Ramp %
40007
BS05
Humidifier State
40005
BS03b5
Free Cooling Ramp %
-
BS06
Dehumidifier State
40006
BS03b6
Heating Ramp %
40008
BS07
Humidification Ramp %
-
BS08
De-humidification Ramp %
-
BS09
Free Cooling Status
-
BS0A
Return Temp
40009
BS0B
Return Temp Set-point
-
BS0D
Supply Temp
-
BS0F
FC Fluid Temp
-
BS15
Supply Temp SP
-
BS11
# Of Present Events
-
BS13
Humidity Lockout Active
40015
bs15
Reheat Lockout Active
40016
bs16
Sensor A Temp
-
BS17
Optional External Sensor
Sensor B Temp
-
BS19
Optional External Sensor
Sensor C Temp
-
BS1B
Optional External Sensor
Comp 1 Temp
-
BS1D
Comp 2 Temp
-
BS1F
Return Humidity
40010
BS21
Return Humidity Setpoint
-
BS22
Sensor A Humidity
-
BS23
Optional External Sensor
Sensor B Humidity
-
BS24
Optional External Sensor
Sensor C Humidity
-
BS25
Optional External Sensor
Conditioner Run Hours
40011
BS26
Compressor 1 Run Hrs
40012
BS28
Compressor 2 Run Hrs
40013
BS2A