SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Ground Overcurrent
40289:05
289:05
BA01_x:05
Transformer Overtemp
40289:06
289:06
BA01_x:06
Ground Fault
40289:07
289:07
BA01_x:07
Ground Failure
40289:08
289:08
BA01_x:08
Liquid Detected
40289:09
289:09
BA01_x:09
Security Alarm
40289:10
289:10
BA01_x:10
Phase Rotation/Loss
40290:00
290:00
BA02_x:00
Datawave Overtemperature
40290:01
290:01
BA02_x:01
Emergency Shutdown
40290:02
290:02
BA02_x:02
Load On Bypass
40290:03
290:03
BA02_x:03
Local Alarm #1
40290:04
290:04
BA02_x:04
Local Alarm #2
40290:05
290:05
BA02_x:05
Custom Alarm #1
40290:06
290:06
BA02_x:06
Custom Alarm #2
40290:07
290:07
BA02_x:07
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N